| Model | B7 (Type 700, B700) pressure switch, explosion proof enclosure |
|---|
| Ordering code | B7 + switch element + seal + X and options + range, e.g. B724BXFS3000# |
|---|
| Enclosure | Epoxy coated aluminum (standard) or 316 stainless steel (option YW); meets Div. 1 & 2, NEMA 7, 9 and IP66. Cover unscrews |
|---|
| Hazardous locations | Class I, Div. 1, Groups B, C & D; Class II, Div. 1, Groups E, F & G (UL; CSA with option C8) |
|---|
| ATEX / IECEx (option CN) | Sira 02ATEX1391X; IECEx SIR 14.0077X; CSAE 21UKEX1056X. II 2GD, Ex db IIC T6 Gb, Ex tb IIIC T85°C Db, Ta –20°C to +60°C; process temperature –20 to 60°C (–4 to 140°F) |
|---|
| Ranges | Pressure: 15, 30, 60, 100, 200, 400, 600, 1000 and 3000 psi. Vacuum: 30 in. Hg. Compound: 30 in. Hg vac/15, 30 or 60 psi. In. H2O: 10, 30, 60, 100 and 150. In. H2O compound: 15 vac/15 and 30 vac/30 |
|---|
| Setpoint | Generally 15% to 100% of range on increasing pressure. Field adjustable (set at about 90% of range as received) or factory set (FS); 7/8″ adjustment nut inside the enclosure |
|---|
| Setpoint repeatability | ±1% of full range (additional setpoint shift of 1% of range per 50°F from initial setpoint set at 70°F typical) |
|---|
| Deadband | Fixed; approximate values by range, switch element and seal material are in the data sheet. Variable deadband element 50: 0.5% to 9% of range |
|---|
| Switch elements | UL/CSA listed. SPDT: 20, 21, 22, 23, 24 (standard), 25, 26, 27, 31, 32, 42, 50. Dual (2 SPDT, not independently adjustable): 61, 62, 63, 64, 65, 67, 68, 70, 71, with terminal blocks standard. Manual reset elements 28 and 29 are not available on the B7 |
|---|
| Electrical ratings | Standard element 24: 15A 125/250/480 Vac, ½A 125 Vdc, ¼A 250 Vdc; 6A 30 Vdc. Heavy duty AC (23): 22A 125/250 Vac. Heavy duty DC (25): 10A 125 Vac or dc. Gold contacts (31, 42, 70, 71): 1A 125 Vac |
|---|
| Actuator seal and process temperature | Buna-N (standard), 0 to 150°F; Viton, 20 to 300°F; Teflon, 0 to 150°F; 316L stainless steel, welded, 0 to 300°F; Monel, welded, 0 to 300°F. Stainless steel and Monel: pressure ranges to 1000 psi only. With ATEX / IECEx (CN): –20 to 60°C (–4 to 140°F); other limits are possible with different diaphragm materials |
|---|
| Proof / burst pressure (psi) | In. H2O ranges (incl. compound): 20 / 35. 30 in. Hg vacuum and compound: 250 / 400. 15 to 60 psi: 500 / 1500. 100 and 200 psi: 1000 / 3000. 400 and 600 psi: 2400 / 3000. 1000 and 3000 psi: 12000 / 18000 (proof 4000 with welded SS or Monel) |
|---|
| Ambient temperature | –20°F to 150°F (–28°C to 65°C); all units calibrated at 70°F |
|---|
| Pressure connection | ¼ NPT female (standard). 316 SS options: ½ NPT male x ¼ NPT female (06, standard on 1000 and 3000 psi), ½ NPT female (07, not with Monel), ¼ NPTF for in. H2O ranges (TA). 7/16-20 SAE female (05) |
|---|
| Electrical connection | Two ¾ NPT female conduit holes, one with a permanent plug; external ground screw. Options: ¾ to ½ NPT bushing (JL), M20 x 1.5 adapter (JM), terminal block (K3, standard on duals), leads potted in a ¾″ sealed conduit (PM), 6 ft leads (LE) |
|---|
| Approvals | UL E38812; SIL 3 capable. Options: CSA approval for NEMA 7 enclosures (C8); ATEX / IECEx (CN); dual seal rating (D2, psi and vacuum ranges); FM approval (FM) or FM approval without pilot light (FT); UL gas/oil limit control to 600 psi (G6, Buna-N or Viton seal) |
|---|
| Factory options | Secondary chamber with vent (G7, 316L SS seal, Teflon backup diaphragm); fire safe welded actuator (G9, 316L SS seal); high static pressure actuator (HX, in. H2O ranges); 3-A sanitary seals, 1½″ (Y53A) or 2″ (Y63A), glycerin filled; cleaned for oxygen service (6B; not with Buna-N, in. H2O ranges or the sanitary seals); silicone free (YF; Buna-N, Viton or Teflon seal, 15 to 600 psi) |
|---|
| Quoted on request | NACE MR-01-75 (MA), #2114, leads over 6 ft, other diaphragm seal assemblies and ranges not listed above |
|---|
| Mounting | Three external surface-mounting holes, or directly on the pressure line. Brackets: 2″ pipe (TM) or wall (BP, in. H2O ranges) |
|---|
| Weight | 2.7 lb (1.2 kg) psi ranges; 3.6 lb (1.6 kg) in. H2O ranges |
|---|